TBP-0-4.6,TBP-O-4.6,TBP-0-7.6,TBP-O-7.6,TBP-A-7.6/131,TBP-B-7.6/131,TBP-C-7.6/131,TBP-A-7.6/85,TBP-B-7.6/85,TBP-C-7.6/85,TBP-A-10.5/131,TBP-B-10.5/131,TBP-C-10.5/131,TBP-A-10.5/85,TBP-B-10.5/85,TBP-C-10.5/85,TBP-A-12.7/131,TBP-B-12.7/131,TBP-C-12.7/131,TBP-A-12.7/85,TBP-B-12.7/85,TBP-C-12.7/85,TBP-B-42/200,TBP-C-47/200,TBP-B-42F/310,TBP-C-42F/310,TBP-A-7.6F,TBP-B-7.6F,TBP-C-7.6F,TBP-A-10.5F,TBP-B-10.5F,TBP-C-10.5F,TBP-A-12.7F,TBP-B-12.7F,TBP-C-12.7F,TBP-B-42F,TBP-C-42F,TBP-B-12.7/131-J,TBP-B-12.7/85-J,TBP-B-12.7/J, TBP-B/F-10.5組合式過電壓保護器,TBP-B/F-12.7
JBP-HY5CD2-12.7/41×29過電壓保護器試驗方法
按原理圖將相關儀表和設備連接好。測試前應*先將電流繼電器LJ的整定值調至*小值(作為后備保護),然后將試驗變壓器空載升壓,電流繼電器LJ應不動作,將數字電流表A2的量程調至10~20A(5KVA及以下容量試驗變壓器可不加限流電阻R)。
工頻試驗電壓分別加在JBP-HY5CD2-12.7/41×29過電壓保護器的A和D、B和D、C和D、A和C、B和C、以及A和B上,緩慢調高試驗變壓器的輸出電壓,同時觀察電壓表及數字電流表A2,TBP間隙未擊穿放電時,數字電流表A2的讀數為零或數值很小。當試驗變壓器的輸出電壓達到JBP-HY5CD2-12.7/41×29過電壓保護器的動作值時,JPB間隙被擊穿放電,數字電流表A2的讀數將突增,電流表A1同樣也會有突變現象產生,此時試驗變壓器的高壓輸出電壓值即為該JBP-HY5CD2-12.7/41×29過電壓保護器的工放值。
JBP-HY5CD2-12.7/41×29過電壓保護器安裝及接線方法
a、戶內型過電壓保護器可以水平安裝在各種不同型號的開關柜內,該類產品除直接與開關柜"A"、"B"、"C"三相及接地相("D"相)相連的線鼻子為裸導體外,其余部分被絕緣體封閉,因此它的相間、相對地(或柜體)的距離及對柜體安裝空間要求相應較小,可直接安裝在開關柜的手車底盤內或互感器室內;
b、帶有過電壓動作計數器的JPB過電壓保護器,先將JPB過電壓保護器本體(安裝方式同上)和過電壓動作計數器各自固定好后,通過配備的特制電纜相連,安裝尺寸詳見《過電壓動作計數器說明書》。